Goal What are the Terminations for a 2001 Auxiliary Relay Module 2001 2001 3011 Auxiliary Relays 556 556 Relay Auxiliary Relay Relay not picking Need terminations Need to know the Terminations Need Wiring Terminations Need to configure system jumpers Need to configure jumpers Need module information Need jumper settings changed relay card Adding Auxiliary relay Always note revision and jumper settings and any component removed from any 2001 module being The 2001 3011 Auxiliary Relays 556 556 has 2 internal relays with Form C contacts that can be several different ways System Reset Selective 24 Volts input and System in Alarm There are two designs of this board Revision B and earlier and Revision C and later Actual terminal strip numbers will depend on panel type style ie full size or repack Revision B and earlier K1 not picked P Common N Normally Closed S Normally Open K2 not picked 13 Common 11 Normally Closed H Normally Open Revision C and later K1 not picked P Common 11 Normally Closed N Normally Open K2 not picked S Common H Normally Closed 13 Normally Open Settings For constant 24 Volts Resettable leave JW1 and JW2 in Remove JW1 and JW2 for selective 24 Volts input on 5 or E for K1 M or J for K2 For constant 0V leave in JW6 and JW4 and cutout JW5 and JW3 For 0V in alarm only leave in JW5 and JW3 in and cutout JW6 and JW4 Revision C and later only JW A Remove this jumper for constant open condition between K1 P to Normally open