System Sensor B200S-LF Low Frequency Intelligent Sounder Base
File Preview
Click below to download for free
Click below to download for free
File Data
Name | system-sensor-b200s-lf-low-frequency-intelligent-sounder-base-7624093185.pdf |
---|---|
Type | |
Size | 1.78 MB |
Downloads |
Text Preview
I Ohio Avenue St Charles Illinois 60174 FAX 630 377 6495 AND MAINTENANCE INSTRUCTIONS Frequency Intelligent Sounder Base model is compatible with System Sensor Models MDL MDL3R MDLW MDL3W and SYNC 1 Diameter Height less sensor Temperature Range Humidity Range Supply Electrical Ratings Supply Voltage Current Current Electrical Ratings Operating Voltage Standby Current Output Volume Volume to 33 VDC VFWR maximum VDC volume setting 70 mA maximum 33.0 VDC 90 mA maximum 24.0 VDC 140 mA maximum 16.0 VDC to 32 VDC maximum base only refer to applicable sensor specification inch 17.46 cm inch 5.08 cm lb 272 gm to applicable sensor Operating Temperature Range using the Base Sensor Cross Reference Chart at systemsensor com to 93 relative humidity non condensing volume setting 15 mA maximum 33.0 VDC mA maximum 24.0 VDC mA maximum 16.0 VDC than 85 dBA minimum measured in a UL reverberant room at 10 feet 24 Volts in continuous tone than 75 dBA minimum measured in a UL reverberant room at 10 feet 24 Volts in continuous tone INSTALLING System Sensor Applications Guide for System Smoke Detectors which provides detailed information on sensor spacing placement wiring and special applications This manual is available from System NFPA 72 and NEMA guidelines should be observed The National Fire Code NFPA 72 requires effective January 1 2014 that audible appli installed in sleeping areas produce a low frequency alarm signal that be a square wave or provide equivalent awakening ability with a funda frequency of 520 Hz 10 200 Series sounder bases are not compatible with remote test capable series detectors This manual should be left with the owner user of this equipment The detector used with this base must be tested and maintained following NFPA 72 requirements The detector should be cleaned at once a year DESCRIPTION B200S LF low frequency sounder base is used with System Sensor 200 Se sensor heads or equivalent For a list of compatible sensors refer to the Sensor website at www systemsensor com Refer to the appropriate for more information on sensors B200S LF low frequency sounder base generates a low frequency tone 520 Hz Studies have shown that low frequency audible devices that op around 520 Hz are more effective in waking individuals in sleeping areas sounder base is capable of producing a variety of tone patterns including distinctive three pulse temporal pattern ANSI Temporal 3 fire alarm sig now required by NFPA 72 for commercial and residential applications The offers maximum flexibility in configuration and operation to meet or the requirements of UL268 and UL464 for Continuous Temporal 3 and time patterns The temporal 4 pattern meets all requirements of UL268 UL2075 as well as private mode setting of UL 464 B200S LF can be commanded by the Fire Alarm Control Panel to adopt address of the attached sensor head but as a unique device type on the By using the address the fire alarm control panel can command an sounder base to activate or a group of sounders in a suite or other configuration The command set from the panel can be tailored to specific event allowing selection of volume tone and group The device two volume levels 75 dBA and 85 dBA The available tones are Contin ANSI Temporal 3 ANSI Temporal 4 and March Time In addition some alarm panels will offer the ability to command a custom tone pattern to the appropriate fire alarm control panel manual for more information as a component of the general evacuation signal producing an NFPA compliant Temporal 3 pattern in synchronization with other System notification devices This requires connection to a power supply of generating the System Sensor synchronization pulses a FACP NAC configured to System Sensor synchronization protocol or a separate module sounder base is intended for use with intelligent systems In addition to connected to the SLC the sounder base requires a connection to either VDC constant power or a NAC circuit depending on the FACP and intended The connections for 24V constant NAC power and the communication are isolated to prevent electrical interaction between them connected to a NAC power is supervised via the NAC circuit supervision in standby mode EOL resistor required for Class B operation when the B200S LF provides supervision of NAC power see Figure 5 using a FACP equipped with a base standby power monitor mode see table and constant 24 V power power supervision EOL de supervision relays and resistors should not be used see Figure 4 In case the B200S LF will provide supervision in both standby and alarm mode If your FACP is not listed in the table or you choose not to use base standby power monitoring mode power supervision relays EOL resistors are required to provide supervision in standby mode If the FACP base standby power monitoring mode is en connecting B200S LF low frequency sounder bases to the NAC will re in power supervision failure when in standby Only connect B200S LF frequency sounder bases to constant 24 V power in this case Refer to the manual for maximum allowable number of units per loop For NFPA72 Installations the Temporal 3 tone at high volume should be for public mode evacuation The use of other tone styles and low volume will be at the discretion of the local Authority Having Jurisdiction AHJ When not used as a supplementary evacuation system the external 24 supply shall be treated as a component of the main power supply system and fall under the requirements of the main power supply system per NFPA 72 EQUIPPED WITH STANDBY POWER MODE Model Revision Series 20 or Higher 20 or Higher 20 or Higher 2.4 or Higher addition the B200S LF is equipped with the circuitry to recognize the Sensor synchronization protocol enabling the sounder base to be Series Knight Knight Knight Knight Knight Knight Knight Controls Controls Controls Revisions 21 or Higher 21 or Higher 21 or Higher 13 or Higher 13 or Higher 13 or Higher 21 or Higher 21 or Higher 21 or Higher 5820XL EVS 13 or Higher IFP 2000ECS 4 or Higher IFP 1000ECS 13 or Higher IFP 100ECS 13 or Higher the sensor GUIDELINES wiring must be installed in compliance with the National Electrical Code the local codes having jurisdiction and must not be of such length or wire which would cause the base to operate outside of its published specifica The conductors used to connect smoke sensors to control panels and devices should be color coded to reduce the likelihood of wiring Improper connections can prevent a system from responding properly the event of a fire sizes up to 12 AWG 2.5 mm2 may be used with the base The sounder will be shipped with the screw terminals set for 14 AWG wiring If 12 wire is to be used back out the screws to allow the wire to fit beneath clamping plates For best system performance the power and wires the communication circuit wires should be twisted pair or shielded cable in a separate grounded conduit to protect the communication loop electrical interference 1 2 the B200S LF mounting plate directly to an electrical box The plate mount directly to 4 square with and without plaster ring 4 inch octa 3 1 2 inch octagon single gang or double gang junction boxes Connect field wiring to terminals as shown in Figure 1 and 2 Attach the mounting plate to the junction box as shown in Figure 3 To mount the sounder base hook the tab on the sounder base to the groove the mounting plate Then swing the sounder base into position to engage the pins on the with the terminals on the mounting plate Secure the sounder base by tightening the mounti