Technical Field Bulletin Flame rating of duct smoke detectors of System Sensor duct smoke detectors Application Engineers 7 03 1 04 duct detectors manufactured by System Sensor are designed according to the National Fire Protection Association NFPA 72 Furthermore our detector is tested to Underwriters Laboratories Standards UL 268 Smoke Detectors for Fire Signaling Systems NFPA 90A Air Conditioning and Ventilating Systems and tested per UL 94 for Flammability ratings is in the opinion of the NFPA 90A Chapter 4.3.3.1.2 2002 edition that duct detectors are exempt from having to meet the criteria of flame spread index or smoke developed index requirements understand the importance of the Uniform Mechanical Code 1994 and the building code that it establishes you have any questions concerning System Sensor products or their application contact Technical Services at 1 800 SENSOR2 736 7672 extension 2 Ohio Avenue St Charles IL 60174 Phone 800 736 7672 Fax 630 377 6583 www systemsensor com