System Sensor M501M EngSpec

File Preview
File Preview
Click below to download for free

File Data

Name system-sensor-m501m-engspec-5416703982.pdf
Type PDF
Size 620.54 KB
Downloads

Text Preview

Product Mini Monitor Module and Engineering Specifications intelligent mini monitor module shall be a System Sensor model number M501M Intelligent monitor modules shall connect one supervised initiating device circuit IDC or zone of alarm initiating devices any normally open dry contact device to the fire alarm panel signaling line circuit SLC Loop modules shall provide address setting means on the module using rotary switches Because the possibility of installation error systems that use binary jumpers or DIP switches to set the address are not acceptable The modules shall also store an internal identifying code the control panel shall use to identify the type of detector Systems that require a special to set the module address including temporary connection at the panel are labor and not acceptable Each module occupies any one of at least 99 possible addresses the SLC loop It responds to regular polls from the system and reports its type and status module shall be no larger than 2 3 4 x 1 1 4 x 1 2 D The IDC zone shall be wired for B Style B only operation The module shall use four 18 AWG color coded pigtail wires a of 6 inches in length with wire insulation removed and tin coated ready for installation UL 864 Control Units and Accessories for Fire Alarm Systems Agency Standards ULC S527 Control Units for Fire Alarm Systems ANSI NFPA 72 National Fire Alarm Code 2009