Wheelock MT4-115 multitone horn install sheet P83159

File Preview
File Preview
Click below to download for free

File Data

Name wheelock-mt4-115-multitone-horn-install-sheet-p83159-1795084362.pdf
Type PDF
Size 810.36 KB
Downloads

Text Preview

INSTALLATION INSTRUCTIONS MULTITONE APPLIANCES MT4 115 this product according to this instruction manual Please keep this instruction manual for future reference Ensure all fuses used on signaling circuits are rated to handle the maximum inrush or peak current from all appliances those circuits Failure to do this may result in loss of power to the signaling circuit and the failure of all appliances on that to operate which could result in property damage and serious injury or death to you and or others Multitone Appliances are UL Listed under Standard 464 for Fire Protective Signaling Service They are listed for both indoor and use with the backboxes specified in these instructions see Mounting Options MT4 115 Multitone Appliances can be field set to any one of eight commonly used alarm tones Sound output can be field set to provide either HIGH HI dBA or STANDARD STD sound output level All inputs have DC blocking capacitor for compatibility with supervision when used with a Fire Alarm Control FACP Multitone Audible Appliances produce a brief inrush current that lasts for just 50 microseconds but can reach a peak value of 5.0 Amps If MT4 115 Multitone Appliances are operated within 15 inches of a person ear they can produce a sound pressure that exceeds the maximum 120 dBA permitted by ADA and OSHA rules Exposure to such sound levels can result in damage a person hearing Please read these instructions carefully before using this product The MT4 115 Multitone Appliance must be field set the desired dBA sound output level and alarm tone before they are installed This is done by properly adjusting a four position in accordance with these instructions Incorrect settings will result in improper performance and could result in property and serious injury or death to you and or others Not recommended for use at refrigerator freezer door entrances or other areas with persistent condensation Switch SW1 of the Multitone Appliance shown in Figure 1 is used to set the desired dBA sound output level and alarm tone The settings are shown below Read these instructions carefully before changing any of these factory settings HERE FOR 0 HERE FOR 1 2 3 4 1 UL Listed Models and Ratings Voltage VRMS Range VRMS 1A dBA and Current Ratings for Multitone Appliances RMS Current AMPS Reverberant at 10 Feet UL 464 Time Horn Horn Tone Whoop AUD factory settings are HIGH dBA SW1 POS 1 set on 1 HORN TONE SW1 POS 2 3 4 set on 1 1 1 1 PC Board Layout Showing Location of Switch SW1 HERE FOR 1 HERE FOR 0 A SMALL SCREWDRIVER TO THE SWITCH POSITION 1 2 3 4 For UL Applications these appliances were tested to the operating voltage limits of 96 132 volts Do not apply 80 110 of these voltage values for system operation 1 Set desired dBA sound output level as follows refer to Figure 2 and Table 2 2 Switch SW1 Settings model is UL Listed for indoor outdoor use with a temperature range of 40oF to 150oF 40oC to 66oC and maximum humidity of RH Ensure the total RMS current required by all appliances that are connected to the system primary and secondary sources do not exceed the power sources rated capacity or the current ratings of any fuses on the circuits to which these are wired Overloading power sources or exceeding fuse ratings could result in loss of power and failure to alert oc during an emergency which could result in property damage and serious injury or death to you and or others calculating the total currents Use Table 1 to determine the highest value of RMS Current for an individual audible across the ex operating voltage range of the audible then multiply these values by the total number of audibles be sure to add the currents for other appliances including audible signaling appliances powered by the same source and include any required safety factors 2 dBA Sound Output Level Settings Level dBA dBA dBA Switch Settings POS 1 Factory Setting 2 Set desired alarm tone as follows refer to Figure 2 and Table 3 Multitone Appliances are field set for any one of eight alarm tones by setting a four position switch SW1 as shown in Figure 2 Table 3 Use SW1 POS 2 3 4 to select the desired alarm tone refer to Table 3 below Branchport Ave Long Branch N J 07740 800 631 2148 www coopernotification comPN P83159FCopyright 2012 Cooper Wheelock Inc dba Cooper Notificationfirealarmresources com NOTES If sheathed multiconductor cable or 3 4 inch conduit fittings are used verify the installed product has sufficient clearance and room prior to installing backboxes and conduit weather resistant installation use outdoor mounting option Outdoor backbox must be mounted vertically with as to allow any moisture or condensation to drain properly through drain holes on bottom of backbox Multitone Appliances can be surface mounted to a standard 4 inch square by 2 1 8 inches deep electrical box Figure A a weather resistant backbox WBB Figure B largest backbox shown in Mounting Options where possible to provide additional wiring room for easy installation entrance to backboxes should be selected to ensure sufficient wiring clearance for installed equipment When exten rings are required conduit should enter through backbox not extension ring Use Steel City 53151 1 1 2 inches deep or inches deep extension rings or equal with same area cut out in back care and proper techniques to position the field wires in the backbox so they use minimum space and produce minimum on the product This is especially important for stiff heavy gauge wires with thick insulation or sheathing not pass additional wires used for other than signaling appliances through the backbox Such additional wires could result in wiring space for the signaling appliance Code 3 Horn and Code 3 Tone incorporate the temporal pattern specified by ANSI NFPA ISO for standard emergency evacu signaling They should be used only for fire evacuation signaling and not for any other purpose Horn and Bell Tones can be used on coded systems with a minimum On Time of 1 4 of a second All other tones are recom for use only on continuous non coded systems Multitone products and these instructions are copyrighted by Cooper Notification and contain proprietary confidential and trade of Cooper Notification No part of the Multitone products and these instructions may be photocopied printed or reproduced in any or modified adapted changed or enhanced or converted to another programming language or used to create updated related or works without the prior written consent of Cooper Notification No part of the Multitone shall be decompiled disassembled or engineered This equipment has been tested and found to comply with the limits for a Class A digital device pursuant to part 15 of the FCC These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a com environment This equipment generates uses and can radiate radio frequency energy and if not installed and used in accordance the instruction manual may cause harmful interference to radio communications Operation of this equipment in a residential area is to cause harmful interference in which case the user will be required to correct the interference at his own expense MATERIAL EXTRAPOLATED FROM THIS DOCUMENT OR FROM COOPER NOTIFICATION MANUALS OR OTHER DOCUMENTS THE PRODUCT FOR USE IN PROMOTIONAL OR ADVERTISING CLAIMS OR FOR ANY OTHER USE INCLUDING DE OF THE PRODUCT APPLICATION OPERATION INSTALLATION AND TESTING IS USED AT THE SOLE RISK OF THE USER COOPER NOTIFICATION WILL NOT HAVE ANY LIABILITY FOR SUCH USE Time Horn Horn Tone Whoop 3 Alarm Tones Description Horn Continuous Factory Setting Hz Modulated 0.07 Sec ON Repeat 0.25 Sec ON 0.25 Sec OFF Repeat ANSI S3.41 Temporal Pattern Hz ANSI S3.41 Temporal Pattern Hz Sweep 4.0 Sec ON 0.5 Sec OFF Repeat Hz Sweep 1.0 Sec ON Repeat Hz 0.25 Sec ON Alternate Settings The Code 3 Horn and Code 3 Tone set on HIGH dBA incorporate the temporal pattern specified by ANSI NFPA for standard evacuation signaling They should be used only for fire evacuation s

Related Files