Edwards 5552 Speaker Install
File Preview
Click below to download for free
Click below to download for free
File Data
Name | edwards-5552-speaker-install-2580493671.pdf |
---|---|
Type | |
Size | 879.32 KB |
Downloads |
Text Preview
and HPSA15 Series Speakers Sheet frequency response level connection W to 4,000 Hz dB UL 10 ft rating 1 in conduit Series and HPSA15 Series are high efficiency UL double re entrant type loudspeakers comply with the requirements of UL Standard 1480 Protective Signaling Speakers are designed to be used in conjunction with control equipment for high intelligibility of audible emergency and protective signals well as voice messages a supervisory capacitor and is suitable for in systems employing supervised circuitry V 70.7 V Maximum supervised circuit voltage is VDC use in ambient temperature ranges from 40 to 1 Power tap selector switch Terminal 2 is the positive terminal 2013 UTC Fire Security All rights reserved 2 3101246 REV 02 REB 15FEB13 2 Mounting dimensions conform with UL requirements wires must be connected as shown in wiring diagram see Figure 3 The maximum wire size that can be connected to this device is 18 Gauge 3 Wiring diagram Do not loop wires under screw terminals Break wire run to provide supervision of connection Installation must comply all Building Codes and NFPA guidelines Installation must adhere to N E C and NFPA 70 72 wiring directives and comply with National and Local Building Codes information contact information see www edwardssignaling com 2 3101246 REV 02 REB 15FEB13