Notifier Addendum-to-the-AM2020-AFP1010-Installation-Manual

File Preview
File Preview
Click below to download for free

Text Preview

AM2020 AFP1010 INSTALLATION MANUAL the REV C2 DATE 1 19 93 6 Add the following note The use of a DACT NFPA 71 is not permitted when one or more transponders with separate supply s is are present in the system 72 Replace Figure 6 1 with Figures 6 1A and 6 1B shown on the following pages 15707 Rev 15707 A ECN 93 159 6 1A NFPA 71 Central Station Service and Trouble Signal Transmission application is not suitable for separate transmission of sprinkler supervisory conditions For connection of alarm devices refer to Figures 4 12 through 4 16 For additional ratings refer to Appendix A During programming of the AM2020 AFP1010 NFPA menu option 71 must be chosen Ground B B A A FIRE 911A Digital Transmitter be physically located in the same as the control panel All connections between the panel and the transmitter must be in 18 AWG minimum CMX must be programmed software type DACT and 7 and 9 open open loop loop VDC VDC ELR Tabs VDC 6 1A Connections for 911A and CMX 27.6 VDC 2 3 4 5 The use of a DACT NFPA 71 is not when one or more transponders with power supply s is are present in the 15707 Rev A 6 15 93 P N 15707 A ECN 93 159 6 1B Using the MS 5012 as a DACT Table 6 1B ELR Ground B B A A CMX must be programmed software type DACT ELR Tabs 6 1B The use of a DACT NFPA 71 is not permitted when one or more transponders with separate power is are present in the system 15707 Rev A 6 15 93 P N 15707 A ECN 93 159