Notifier FDM-1 Dual Monitor Module

File Preview
File Preview
Click below to download for free

File Data

Name notifier-fdm-1-dual-monitor-module-4153906827.pdf
Type PDF
Size 451.67 KB
Downloads

Text Preview

INSTALLATION AND MAINTENANCE INSTRUCTIONS Dual Monitor Module Operating Voltage 15 to 32 VDC Current Draw 5.7 mA LED on Operating Current 750 LED flashing Resistance 47K Ohms IDC wiring resistance 1,500 Ohms Range 32 to 120 0 to 49 10 to 93 Noncondensing 41 2 H x 4 W x 11 4 D Mounts to a 4 square by 21 8 deep box SMB500 Electrical Box Clintonville Rd Northford CT 06472 1653 484 7161 Installing information is included as a quick reference installation Refer to the control panel installation manual for detailed information If the modules will be installed in an existing system inform the operator and local authority that system will be temporarily out of service Disconnect power to control panel before installing the modules This manual should be left with the owner user of this Description Dual Monitor Module is intended for use in intelligent two systems It provides two independent 2 wire initiating device IDC at two separate consecutive addresses It is capable monitoring normally open contact fire alarm and supervisory or either normally open or normally closed security de The module has a single panel controlled red LED Requirements ensure proper operation this module shall be connected to a Notifier system control panel list available from Noti directly to 4 square electrical boxes see Figure 2A The must have a minimum depth of 21 8 Surface mounted elec boxes SMB500 are available from Notifier All wiring must conform to applicable local codes or and regulations This module is intended for limited wiring only Install module wiring in accordance with the job drawings and wiring diagrams Set the address on the module per job drawings Note Some panels support extended addressing In order to set the module above address 99 on compatible systems carefully remove the stop on the upper rotary switch with thumb in the direction shown in Figure 1 Note Monitor module L using terminals 6 and 7 re at the address set on the code switches Monitor H using terminals 8 and 9 will automatically re at the next higher address For example if the code are set to 76 module L will respond at address 76 module H will respond at address 77 Use caution to duplicate addressing of modules on the system Secure module to electrical box supplied by installer as in Figure 2A 1 Removing Switch Stop 865 2A Module mounting 2B 10 2 1 1 I56 1463 02 3 Typical 2 wire initiating circuit configuration NFPA Style B INITIATING DEVICE CIRCUITS L H POWER LIMITED TO 230 A 12VDC MAX NEXT K EOL K EOL NUMBER OF UL LISTED CONTACT CLOSURE MAY BE USED DO NOT MIX FIRE INITIATING SUPERVISORY OR SECURITY DEVICES ON THE SAME INITIATING DEVICE CIRCUIT CONTACT CLOSURE DEVICES PER INSTALLATION INSTRUCTIONS 865 LINE VDC MAX PAIR RECOMMENDED A TERMINALS 6 7 RESPONDS AT ADDRESS ON CODE SWITCHES MONITOR B TERMINALS 8 9 AT NEXT HIGHER ADDRESS PANEL OR DEVICE MODULES TO LISTED COMPATIBLE CONTROL PANELS ONLY WIRING SHOWN IS SUPERVISED AND POWER LIMITED 2 I56 1463 02 Notifier

Related Files