Potter IPA Series Addressing PAD Detectors & Modules

File Preview
File Preview
Click below to download for free

File Data

Name potter-ipa-series-addressing-pad-detectors-modules-5320491678.pdf
Type PDF
Size 855.17 KB
Downloads

Text Preview

Addressing PAD Protocol Detectors Modules PAD detectors and modules addresses are set by changing the dip switches located on each device An address must be set prior connection Addresses addresses are comprised of a seven 7 position dip switch used to program each device with an address ranging from 1 to the table below to set dip switches on any PAD detector or module Each box indicates that the dip switch is and each box indicates 16 32 64 16 32 64 16 32 64 16 32 64 16 32 64 16 32 64 16 32 64 16 32 64 16 32 64 16 32 64 examples shown below illustrate a PAD device dip switch settings the 1st example shows a device not addressed where all dip settings are in the default position the 2nd illustrates an addressed PAD device via the dip switch settings 4 64 4 64 4 64 dip switches are set to the position Not Addressed switches set for address 42 2 8 32 are switches set for address 90 2 8 16 64 are PAGE 1 OF 1 Electric Signal Company LLC St Louis MO Phone 800 325 3936 www pottersignal com8870029 REV B 12 16IPA Series Addressing PAD Detectors Modulesfirealarmresources com