Siemens ABHW-4B Cerberus PRO Audible Base (with Loop Power Option), Data Sheet

File Preview
File Preview
Click below to download for free

Text Preview

Detection Bases Audible Sounder Base with Loop Power Option ABHW 4B AND ENGINEER SPECIFICATIONS Sheet Innovative two wire loop power option Highly flexible programming and configuration options independently controlled outputs by device Provides six 6 field configurable audible tone patterns Steady American National Standards Institute ANSI Temporal 3 ANSI Temporal 4 Carbon Monoxide CO Temporal 4 Low Power March time 120 and Canadian March time 30 Power options include NACs Loop two wire Siemens PAD series NAC Extenders Model ZIC 4A for FireFinder XLS FACPs Any other UL Listed 24VDC regulated power supply Compatible with Cerberus PRO intelligent detectors Siemens and devices ABHW 4B View ABHW 4B View Synchronization by loop Standard 3,000 Hz Buzzer tone UL268 UL464 UL2075 Listed ULC S529 Listed FM 3230 3010 and CSFM Approved Overview Model ABHW 4B Audible Sounder Base from Siemens Inc is an intelligent supervised and addressable base designed for use in standard applications an audible notification device Each Model base generates a 3,000 Hz audio signal that with NFPA 72 Standard ABHW 4B is UL ULC Listed and is the first ever audible base to have the option of being directly from a signal line circuit SLC in a two configuration when used with a Cerberus PRO The loop power feature and advanced options contained with each audible base are not available when a Siemens Model detector is used Though Model ABHW 4B will similar to that of a Model ADBH 11 audible base a Model or detector is used innovative loop power option provides easier two wire for new or expansion applications where wiring or power options are limited Model can also be powered in a traditional four wire utilizing a notification appliance circuit a Siemens PAD series NAC extender Model ZIC 4A any UL Listed 24VDC regulated power supply PRO Safety Products See the Model ABHW 4B Installation and Operation IOM A6V10405587 for further information ABHW 4B provides six 6 field configurable tone two 2 volume levels are used with compatible detectors and FACPs Steady Temporal 3 Temporal 4 pattern Temporal 4 with low power Time 120 and Canadian March Time 30 are by each intelligent audible sounder base audible sounder bases wired in the same circuit are fully synchronized with the PRO Advanced Line and Standard Line detectors support the Siemens Remote Lamps Models RL HC RL HW used in conjunction with agency listed Siemens fire components Model ABHW 4B be used in lieu of a single multiple station smoke to achieve enhanced system level functionality intelligent addressable audible sounder base of a standard Siemens Fire Safety Series layout combined with supportive circuitry Cerberus PRO and Model of detectors Audible Sounder Base for infrastructure FC901 24 Software tool v01.02.16 53 Intelligent Detectors Data continued Ratings Voltage max max power 16 33 VDC power 16 33 VDC SLC loop 250 external source 20 dBA 7.5 mA dBA 4.5 mA dBA 8.0 mA dBA 3.5 mA Cross Cable 18 AWG Wire Gauge 2 back end blocks of up to four screw terminals on each side for Ordering S54320 F13 A1 Audible Sounder Base Loop Power Option Audible Base S54320 F13 A2 tone COO USA Optical Heat Detector Heat Detector Optical Detector S54320 F7 A2 Dual Optical Heat Detector S54320 F8 A2 Dual Optical Heat w CO Detector Remote Lamps Remote Alarm Lamp Wall Remote Alarm Lamp Ceiling Model Detectors Optical Heat Detector Heat Detector Optical Detector Optical Heat Detector Heat Detector Optical Detector Models SFP 11 SFPO 11 and SFPT 11 detectors are approved in Canadian installations Model bases limited in audible base functionality Technical Support at 1 800 248 7976 for further details ABHW 4B houses a pre wired audible sounder device of generating a 3,000 Hz tone that provides a signal up 85dBA at 10 feet 3.1m for localized annunciation different power options are available to provide power the Model ABHW 4B audible base Additionally all Model bases are capable of sounding simultaneously or in any combination depending upon the configuration used on a Siemens FACP For power and wiring options see IOM A6V10405587 Model ABHW 4B is a UL ULC Listed supplementary device that meets or exceeds the 85dB at 10 3.1m audibility requirement specified in UL268 ULC ULC S529 as well as UL464 UL2075 except for low frequency tone requirements with s FACPs ABHW 4B functions with the following Type XLS Machine Interface PMI or later Custom Configuration Software or later Loop Card Model DLC or later PRO 50 point FACP FC922 FC924 v6.0.0R1 or later Data smoke detectors used with Model ABHW 4B are subject to maximum 30 ft center spacing 900 sq ft as referred to the National Fire Protection Association Standard 72 This however is based on ideal conditions namely ceiling no air movement and no physical obstructions the fire source and the detector not mount detectors in areas close to ventilating or air outlets Exposed joists or beamed ceilings may effect safe spacing limitations for detectors It is for NFPA 72 guidelines be applied to detector and spacing Data Properties Temperature 120 0 49 Humidity 95 non condensing Output Box 85 dB 75 dB cm 4 inch square gang box A 4 10.2 cm octagon box is not compatible with Model ABHW 4B Cerberus PRO Industry Inc Building Technologies Div Fernwood Road Florham Park NJ 07932 973 593 2600 Fax 908 547 6877 www USA Siemens com Cerberus PRO Technologies Division Fire Safety in U S A The information contained in this data sheet document is intended only as a summary and is to change without notice The devices described here have specific instruction sheets cover various technical limitation and liability information of these instruction sheets and the General Product Warning and Limitations which also contains important information are provided with the product and available from the Manufacturer contained in these documents should be consulted before specifying or using the product further information or assistance concerning particular problems contact the Manu

Related Files