Siemens AD-3I AD-3ILP Air Duct Detectors, Installation Wiring Instructions

File Preview
File Preview
Click below to download for free

Text Preview

INSTALLATION WIRING INSTRUCTIONS AD 3I and AD 3ILP DUCT DETECTORS AD 3I and AD 3ILP Detectors from Siemens Industry Inc are System 3 PXL System SXL EX System SXL System XL3 System MXL Control Panel and MXL IQ Control Panel compatible air detectors They are designed for use in heating ventilating and air duct systems Model AD 3I uses ionization smoke detectors Model AD 3ILP uses photoelectric smoke detectors to detect the pres of combustion products in a duct system Refer to TECHNICAL below for information on compatible detectors smoke or combustion products are detected shutdown of the duct and or operation of supplementary equipment is provided by the system control panel DATA Detector Compatibility 1 COMPATIBILITY Control Panel Control Panel CZM 1 1B6 or CZM 4 3 PXL PXL PZE 4B SXL SXL SZE 4R SXL SZE 8A SXL EX SXL EX SZE 4X SXL EX SZE 8AX XL3 INX 3 XL3 ZNX 3 Detectors DI B3H ILI 1BH DI B3H no accessories with CZM 1 1B6 DI B3H DI B3H DI B3H DI B3H no accessories DI B3H no accessories DI B3H no accessories DI B3H DI B3H DI B3H ILI 1BH DI B3H Industry Inc Technologies Division Park NJ 315 093234 7 Building Technologies Ltd Safety Security Products Kenview Boulevard Ontario 5E4 Canada 2 COMPATIBILITY Control Panel XL3 INX 3 Detectors ILP 2 ILP 2 is only compatible with MXL MXLV Rev 8.0 or greater firmware and MXL IQ 3.0 or greater firmware When the CSG M is configured the DUCT application must selected NOT USE air duct detectors with Alarm Verification 3 DATA cid 21 cid 26 cid 27 cid 19 cid 21 cid 17 4 DUCT CONDITIONS Range 32OF 0OC 100OF 38OC per UL 268 268A Range ILI 1B ILI 1BH altitude limitations feet feet Humidity Range 0 93 non condensing per UL 268 268A Duct Velocity Range 500 4000 ft min AD 3I ft min AD 3ILP Tube Pressure Range of Differences inches of water column for AD 3I inches of water column for AD 3ILP These air duct detectors are designed for detection and con of products of combustion in a duct system They are not be used for open area protection the AD 3I 3ILP AD 3I or AD 3ILP is operating a sample of air is from the duct and passed through the sampling chamber at low ve by means of the inlet sampling tube The air sample passes through smoke detector mounted in the duct housing and is exhausted back the duct through the outlet sampling tube Indication System 3 System SXL EX System SXL System XL3 MXL MXL IQ Panel and System PXL all have LEDs for alarm indication that are with the AD 3I 3ILP Condition used with the CP 2ER MXL MXL IQ Control Panel System PXL SXL EX System SXL System 3 or System XL3 the Model AD 3I operates directly from the control panel An alarm condition on any of systems is indicated by visual and audible system devices On XL3 the alarm is also indicated on the DAX module and any optional used On MXL Systems the alarm is indicated on the Control Panel and on the optional printer See system manuals for further infor a fire is extinguished and all products of combustion are cleared from duct system each system can be reset at its respective control panel remote annunciator if available Condition trouble condition from an AD 3I 3ILP is indicated by visual and audible on the control panel in the CP 2ER System 3 System SXL EX SXL System XL3 MXL MXL IQ Control Panel or System PXL on the type of system in which it occurs On System XL3 and Control Panels it also may be indicated by an optional printer your Authorized Siemens Industry Inc Service Representative when a occurs further information refer to the appropriate Operating Instructions OPERATING INSTRUCTIONS P N 315 193524 Control Panel OPERATING INSTRUCTIONS P N 315 092117 Control Panel OPERATING INSTRUCTIONS P N 315 093626 PXL OPERATING INSTRUCTIONS P N 315 094211 SXL EX OPERATING INSTRUCTIONS P N 315 094999 SXL OPERATING INSTRUCTIONS P N 315 092419 3 OPERATING INSTRUCTIONS P N 315 084881 XL3 OPERATING INSTRUCTIONS P N 315 082989 THE AIR DUCT HOUSING on Duct System the air duct detector in the main supply duct downstream from the and positioned so as to operate reliably in case of smoke in any part the air stream In instances where filters are capable of removing install detectors both upstream and downstream from the filters air duct detectors use sampling tubes which monitor the full width of an duct to overcome the limitations of spot type smoke and heat detectors the duct However since stratification can occur in the air stream after a duct run locate the detector after bends or inlets which create turbu and hence a more homogeneous mixture of air The detector should possible be located a minimum of six duct widths downstream from the of the turbulence See Figure 1 A 12 inch by 12 inch access hole be cut in the duct adjacent to the detector to permit checking and of the sampling tubes if necessary TUBE TUBE LEAST SIX WIDTHS 1 Mounting of Duct the air duct detector in the air handling system as shown in Figure and in conformance with NFPA Pamphlet No 90A Air Conditioning Ventilating System and with NFPA 72 National Fire Alarm Code publications are available from the National Fire Protection Associa Batterymarch Park Quincy Ma

Related Files