Siemens FC2005 Desigo 50-Point Addressable Fire Alarm Control Panel, Data Sheet
File Preview
Click below to download for free
Click below to download for free
File Data
Name | siemens-fc2005-desigo-50-point-addressable-fire-alarm-control-panel-data-sheet-3180924756.pdf |
---|---|
Type | |
Size | 1.04 MB |
Downloads |
Text Preview
Product Overview FC2005 is an intelligent FACP that a cost effective feature rich solution small fire alarm system applications and compact in design Model FC2005 is for small fire protection applications using than 50 addressable devices Typical usages retail outlets strip malls medical restaurants banks etc Desigo Fire Safety Addressable Fire Alarm Panel FACP FC2005 Architect and Engineer Specifications Main board Model FCM901 U3 Amps 170 Watt power supply Model FP2011 U1 enclosure Model FH901 U3 R3 System features Fire alarm control panel FACP for up 50 addressable points that is System features of the following three 3 components Main board Model FCM901 U2 50 addressable devices on one 1 Class A or two 2 Class B remote printer FCA2018 U1 Amps 170 Watt power one 1 Class A or two 2 Class B notification appliance Model FP2011 U1 NACs enclosure digital alarm communication transmitter DACT releasing scenarios FH901 U2 R2 System features stations isolation devices such as PAD 5 X Series I Os and XMS Optional connectivity to a city tie module FCI2020 U1 RS connection remote annunciators and non 24VDC auxiliary Off normal warning Carbon Monoxide CO detection remote printer Model FCA2018 U1 RS connection for remote annunciators prints system event history detector sensitivity 50 addressable devices one 1 Class A or two 2 B circuits one 1 Class A or two Optional connectivity to a leased line city tie module Model Class B notification circuits NACs digital alarm transmitter Off normal warning message prior to reset releasing scenarios isolation devices such PAD 5 X Series I Os and X Manual stations Carbon Monoxide CO prior to reset programmable front control and easy set up with tool a 182 character UL 864 10th Edition Listed and non resettable 24VDC auxiliary power and easy set up with custom configuration tool programmable front panel control Alphanumeric keypad manual configuration CSFM NYC Fire Approved of Chicago Class 1 Approval S527 3rd Edition Approval not approved for use in prints system event detector sensitivity Model FC2005 its built in DACT and two 2 NACs Model is powerful enough to economically the needs of these applications 50 point FACP has City of Chicago Class 1 as well as being FM 3010 CSFM 0259 FDNY 6104 and UL 10th Edition and ULC S527 3rd Edition Infrastructure Building Products usa siemens com fire Data Sheet 6813 Model FC2005 FACP consists of a main board Model a 170 Watt power supply Model FP2011 and a Model FH901 U2 R2 system enclosure The software for Model FC2005 is held in flash erasable programmable read only memory Board Model FCM901 U2 main board provides system display control as well as connections for system field wiring removable terminal blocks 3.5 inch 8.9 centimeters by 1.5 3.8 centimeters display screen shows all system and event status Each screen supports 182 seven 7 lines with 26 characters per line event may have a custom message up to 40 that describes the event location backlit LCD screen illuminates on any system event or key press New events are by a flashing exclamation point Once the exclamation point changes to a check A system status line shows the quantity of presently active each main board contains a built in RS bus Model FCM901 U2 readily supports Power Trouble Supervisory and Ground Fault system diodes LEDs are also LEDs to indicate when audible circuits are or The main board supports four 4 buttons including Acknowledge Alarm and Manual Alarm ULC jurisdictions Unsilence Reset and User Control system offers an off normal warning feature alerting when active devices are not ready for reset These devices may include manual stations that have not reset smoke detectors with smoke remaining in the chamber etc the main board supports an alphanumeric as well as navigation keys which are used for maintenance functions and system configuration main board supports connection for up to 50 devices via one 1 A or two 2 circuits The loop supports all C NET devices including Desigo Fire Safety intelligent and Model The main board also supports one 1 A or 2 B NACs NAC supports a maximum 2.5 Amps with 2.5 max allowed between the NACs Each NAC can be to a synchronized strobe for horn strobe devices or for devices Audible devices can be set for Temporal 3 Temporal 4 Time 30 60 120 Codes main board supports four 4 C relays for Alarm Supervisory and User Programmable events Each is rated at 2 Amps at 30VDC maximum resistive The board supports two 2 auxiliary 24VDC connections system reset one 1 connection interrupts the power five seconds for use with 4 four wire conventional Each auxiliary power output is 24VDC nominal rated at 0.75 Amps main board contains a built in DACT which provides between Model FC2005 and with the or remote monitoring station The built in DACT two 2 separate programmable accounts as well two 2 connections to the public switched telephone The connections support RJ31X male connectors compatibility with each Model FC2005 FACP see the Station Receiver Compatibility Table on page 4 main board contains a battery charging circuit connection to lead acid batteries rated at 24VDC The main board can charge up to 18 AH batteries main board contains a universal serial bus USB and module firmware upload via the custom tool FC2005 can be configured using the custom tool or manually from t