Siemens OCM-16 Output Control Module, Installation Instructions

File Preview
File Preview
Click below to download for free

Text Preview

Installation Instructions OCM 16 Control Module 5 6 5 6 Model OCM 16 Output Control Module from Industry Inc is a remotely located general output module It provides sixteen open outputs to drive LEDs incandescent lamps or relays There is an additional output for a local and two inputs for momentary lamp test and audible silence switches OCM 16 is mounted in an enclosure that is re located from the Main Panel Communication the OCM and the NIC C is through the Control Network CAN bus Each OCM 16 has two 10 rotary switches that are used to set the board on the CAN which is a sub address of the The 16 outputs of the OCM 16 are controlled by received from the NIC C over the CAN CAN message can activate any or all of the 16 outputs drive LEDs incandescent 24 Volt lamps or relays any of the outputs is activated LEDs lamps relays ON the local audible if installed will sound it is acknowledged by shorting position 19 and 20 TB2 If the outputs are deactivated before the alarm audible is acknowledged the alarm local audible cease to sound shorting terminals 17 and 18 all LEDs or lamps will on to confirm that they are working and automati will return to their normal state after a few sec Both the lamp test and local audible silence on multiple OCM 16s can be connected to a switch one for each function A single audible also be used with multiple OCM 16s 1 Output Control 315 033150 6 Industry Inc Technologies Division Address Switches Set the board address for each OCM 16 using both of ten position rotary switches located on the board See Figure 2 Each of these must be a sub address of the NIC C and must be the same as the assigned in the Zeus Programming Tool LED Incandescent Relay Select Switches When LEDs are used open corresponding dipswitches on S1 and S2 Refer OCM 16 Switches Table to provide a current limiting resistor of 2.7K to each LED When incandescent lamps or relays are used close corresponding on S1 and S2 Refer to OCM 16 Switches Table to bypass the resistors OCM 16 may be installed in a REMBOX When using REMBOX 2 or 4 mount the in one module space on a REMBOX2 MP P N 500 634211 or REMBOX4 MP 500 634212 using the four screws provided Refer to REMBOX2 MP REMBOX4 Installation Instructions P N 315 034211 Up to 4 OCM 16s will fit in a up to 8 OCM 16s will fit in a REMBOX4 all system power before installation first battery then AC To power up the AC first then the battery OCM 16 module is a node in the CAN bus OCM 16 can be installed with or without an RNI Connect 24V and CAN as shown in Figures 2 and 3 to 99 CAN modules in any combination can be connected to the CAN of each NIC C OCM 16 module is shipped with one CCS cable connections for OCM 16 modules are shown in the following table Industry Inc Technologies Division 315 0033150 6 CAN bus requires a 120S resistance at each end of the loop Refer to the NIC C Instructions P N 315 033240 for details about CAN termination All wiring must be in with Article 760 NEC or local building All circuits are power limited NFPA 70 per NEC 760 Electrical Ratings current 14mA max 24VDC current 200mA 24VDC For additonal information to the NIC C Installa Instructions P N 315 All wiring to TB1 must be within the same room within 20 feet in rigid conduit Lamp test switch ACK switch and audible must be UL 864 devices CAN network max line 15S Mount the Lamp Test Ack and Audible Device on REMBOX2 4 front door Wiring for TB1 and TB2 is 18 min 12 AWG max Wiring for TB3 is 18 AWG 16 AWG max Refer to PSC 12 Installation P N 315 for ground fault impedances UP TO 16 LED INCANDESCENT RELAY ANY COMBINATION UNSUPERVISED UP TO 16 LED INCANDESCENT RELAY ANY COMBINATION ON BE SET TO FOR LEDs CAN TERMINATOR 110 134215 P2 or P3 THIS IS THE LAST ON THE PANEL 5 6 5 6 SWITCHES 5 6 5 6 V V RET V V RET NOT USE NOT USE PSC 12 PSX 12 TB3 ANY REGULATED LIMITED POWER LISTED FOR PROTECTIVE USE PSC 12 TB1 NIC C 315 033240 WIRING DETAILS TEST ALARM OPEN MOMENTARY PUSHBUTTON UL 864 LISTED AUDIBLE 50mA MAX UL 864 LISTED 2 Wiring Without An RNI NEXT Industry Inc Technologies Division 315 033150 6 CCS RNI P4 CCL TERMINATOR 110 134215 WITH NIC C 5 6 5 6 5 6 5 6 5 6 5 6 5 6 5 6 3 CAN Bus Connections With An RNI RATINGS CE applications in Cerberus E100 systems refer to Instruction A24205 A334 B844 English or A24205 A334 A844 German Industry Inc Technologies Division Park NJ Building Technologies Ltd Safety Security Products Kenview Boulevard Ontario 5E4 Canada Geb Co oHG M 315 033150 6

Related Files