Siemens PS-35 Power Supply Module, Installation Instructions
File Preview
Click below to download for free
Click below to download for free
File Data
Name | siemens-ps-35-power-supply-module-installation-instructions-4590183762.pdf |
---|---|
Type | |
Size | 610.49 KB |
Downloads |
Text Preview
Installation Instructions PS 35 Supply Module TC 30U Module Model PS 35 stepdown transformer and bridge from Industry Inc provides a rectified full wave 24 output from an input supply of 120 VAC 50 60 Hz input power consists of a main phase with an inde circuitbreaker labeled Reset and a trouble which is separately fused Both inputs use a com neutral 24 volt full wave output is rated at 9 amperes DC full and 6 amperes DC standby load Separate output are provided main and power outputs fused at 15 amps and 2 amps both 5 and 6 provide 1.5A auxiliary output when the is used as a CP 35 system supply For example is rated 24 VDC 1.5A max for internal applications as SR 32 SR 33 or Model RA annunciator located control unit enclosure s used as a separate 24 VDC power supply with bat backup and jumper plug JP PS terminals 5 and 6 provide the full 9A loading Typical wiring when used the TC 30U is shown in the illustration on the back of sheet protection is provided across both the input as well as the DC output Used as Power Supply for Control Panel CP 35 Mount the module to the horizontal mounting in upper right hand position on the top row the control enclosure wiring as necessary Use special plug and assembly CP 35 Panel Refer to CP 35 Wiring Diagram 315 in the Control Panel INSTALLATION AND INSTRUCTIONS for system inter connection Industry Inc Technologies Division Park NJ 315 085062 9 protection cover plate over the terminals making wiring connections Used as 24 VDC Power Supply with Battery Backup TYPICAL WIRING DIAGRAM illustration on reverse Mount module horizontal mounting control enclosure Select a location so that wiring runs are as short possible Note that the PS 35 occupies three positions Connect wiring as necessary When an additional PS 35 Power Supply with plug JP PS is used for extra bell ringing in a CP 35 controlled system with power a transfer module Model is required to supply emergency power the audible signal circuit When battery is not provided the PS 35 output should supervised SR 30 or equal protection cover plate over the terminals making wiring connections Replacement all system power before replacing fuses first and then AC To power up connect AC first then fuses F2 and F3 slide fuse off fuse holders then in new fuses P N 105 224090 15A 250V max P N 105 284845 2A 125V max in and turn counterclockwise Remove fuse from cap with P N 105 224090 15A 250V max Building Technologies Ltd Safety Security Products Kenview Boulevard Ontario 5E4 Canada WIRING DIAGRAM Used As Separate 24 VDC Supply With Battery Backup Used As Power Supply Control Panel of CP 35 CP 35 Wiring P N 315 084902 FU 3.2A Connection Wire Full Wave Rectified 9A Max Application Input VDC 9A Max Note Battery charging connections not shown Designated Load Full Wave Rectified or Backup 9A Max Application Refer to the BI 35 Installation Instructions P N 315 086257 for detailed wiring when using the PS 35 in conjunction with the BI 35 module Refer to P N 315 093680 for all power limited connections Refer to P N 315 050769 for all battery information and battery charger information For the PS 35 TB1 positions 1 2 4 6 are non power limited terminals If power limited is desired for terminals 5 and 6 use the PLM 35 P N 315 093495 For the TC 30U terminals are non power limited For power limited wiring on terminals 5 and 6 use PLM 35 P N 315 093495 315 085062 9