Data MXLV Audio Riser Control Module RCM 1 AND ENGINEER SPECIFICATIONS Peer to peer paging capability Multiple unique page command Audio signal repeater Campus paging and evacuation Style 4 or Style 7 inter panel communication Overview LifeLINK Audio Riser Control Module Model RCM 1 Siemens Industry Fire Safety adds the capability of paging or paging to MXLV networks MXLV systems are generally designed provide full standalone life safety protection voice and paging capability RCM 1 adds the ability to send a live voice to any or all other MXLV standalone that are connected as part of the LifeLINK Model RCM 1 provides a riser that MXLV systems together and operates in various to meet numerous combinations of inter audio communication requirements RCM 1 is designed for applications that call for live paging between buildings such as college campuses facilities other multi building sites applications typically call for independent fire alarm control panels FACPs with live paging within each individual building and between in any combination Model RCM 1 also the option within a single or multi building of multiple unique command consoles or command consoles for paging system control RCM 1 plugs into one 1 full Model OMM 1 or OMM 2 card cage slot and communicates directly Industry Inc Technologies Division LifeLINK MXLV global network voice interface UL 864 9th Edition Listed ULC Listed CSFM NYMEA and City of Chicago Approved the MXLV system via TTL logic Model RCM 1 control and supervision of global page risers in Voice networks The audio communications path each Model RCM 1 module will support any with the use of copper wire cable a combination of copper and fiber optic cable communication path between each Model RCM 1 can be configured to meet the requirements of Style 4 or Style 7 for full bi directional live voice or Style 4 single direction live voice paging All paths are fully supervised isolation is provided between each Model module for an added level of system performance arrangement is particularly essential for campus systems a LifeLINK network voice system using Model RCM 1 each MXLV control panel can be programmed support inter panel paging Panel 1 can send a live page to any zone or group of zones on Panel 2 and versa The ability to transfer the control between command consoles is also programmable This allows multiple paging command consoles to be with the ability to indicate which command has control and the ability to or access to gain control of the paging command Audio Riser Control Module 5058 Overview continued the event of network failure of any form each MXLV still maintains the ability to control the voice page locally In all cases whether a system failure has has not occurred the local system microphone for MXLV panel will always have the highest priority other audio inputs i e pre recorded audio and Humidity Range RCM 1 is UL 864 9th Edition Listed for indoor locations within a temperature range of 120 3 to 32 3 0 2 and at a relative of 93 2 at a temperature of 90 3 Ratings Current Voltage each Model module 24VDC and Operation Manual 315 092882 Control Module Module Note For further details refer to MXLV IOM manual 315 092036 Documentation Sheet Number for Ordering Control Module Module from the local MXL ACM TBM will be to the local speaker zones OCC The audio riser will be switched to the Port C 4 output riser audio output from the local MXL is The audio from the global riser is to the local speaker zones and to C Style 4 output riser audio from the local system is connected to the local speaker output and the global This marketing data sheet is not intended to be used for system design or installation purposes the most up to date information refer to each product installation instructions Industry Inc Technologies Division Safety Fernwood Road Park NJ 07932 973 593 2600 908 547 6877 www SBT Siemens com FIS in U S A Safety Kenview Boulevard Ontario 5E4 Canada 905 799 9937 905 799 9858 2011 sheet dated 9 02

Related Files