Architect and Engineer Specification Patented 2 WIRE Series AS Audible Strobe offers more features with Less Current and Inrush The audible provides a Selectable choice of a continuous horn tone or temporal pattern code 3 when constant voltage from a Fire Alarm Control Panel is applied Each tone has 3 dBA settings to choose All models may be Synchronized when used in con with the Series SM or DSM Sync Module Addi the audible may be silenced while maintaining activation Series AS Audible Strobes are designed for maximum reliability and cost effectiveness while meet or exceeding the latest requirements of NFPA 72 Na Fire Alarm Code ANSI 117.1 American National for Accessible and Usable Buildings and Facili UL Standard 1971 Standard for Signaling Devices The Hearing Impaired and UL 464 Audible Signal Series AS Audible Strobe Appliances when specified and installed in accordance with NFPA standards can provide the Equivalent Facilitation al under ADA Accessibility Guidelines ADAAG Gen Section 2.2 by meeting or exceeding the illumination results from the ADA specified strobe intensity of 75 at 50 feet This is an illumination of 030 lumens square foot When used with the Wheelock Series SM STROBE Listed Approved 20 105A 106A 107A 108A DSM Sync Module synchronization of the continuous tone provides the temporal code 3 tone mandated NFPA 72 1993 with an effective date of July si for all audible appliances Approvals Include Underwriters Laboratories UL 1971 UL464 Listings FCC Part 15 Pending European CE New York City MEA California State Marshal CSFM Chicago BFP and Factory Mu FM on all models ADA NFPA ANSI compliant Meets OSHA 29 Part LOW CURRENT ZERO INRUSH PATENTED 2 Wire Appliance Selectable Continuous Horn or Temporal code 3 3 Selectable dBA levels in both tones Continuous Tone Anechoic 90 95 99 dBA 82 88 or 91 dBA Temporal Code 3 Tone Anechoic 90 95 99 dBA 75 82 or 85 dBA SERIES AS Audible Strobe Appliances available in mount models Wall mount available in 15 15 75 75 and 110 can dela intensity 15 75 candela wall mounted strobes are listed at candela under UL Standard 1971 and meet 75 can intensity on axis for ADA guidelines with low cur draw All models can be Synchronized by adding the Series or DSM Sync Module to the NAC circuit Sync the Audible Maintain the Temporal Pattern 2 or more appliances are in an area Meets NFPA for Temporal Evacuation Notification Sync the Strobe Maintain True 1 Flash per second using 2 or more visual appliances within the field view Meets ADA and NFPA Ability to Silence the Audible while maintaining the flash ALL FEATURES ON 2 WIRES S 10th Street P O Box 610 cid 127 Blue Springs Missouri 64013 0610 U S A cid 127 816 229 3405 cid 127 Fax 816 229 0314 cid 127 www fike com 2002 Issue and Ordering Information warnings are printed in bold capital letters Series AS Strobe products are UL 1971 for indoor use a temperature range of 32 F to 120 F 0 C to 49 and maximum humidity of 85 PLEASE READ THESE SPECIFICATIONS ASSOCIATED INSTALLATION INSTRUCTIONS BEFORE USING SPECIFYING OR APPLY THIS PRODUCT FAILURE TO COMPLY WITH ANY THESE INSTRUCTIONS CAUTIONS AND WARN COULD RESULT IN IMPROPER APPLICATION IN AND OR OPERATION OF THESE PROD IN AN EMERGENCY SITUATION WHICH COULD IN PROPERTY DAMAGE AND SERIOUS IN OR DEATH TO YOU AND OR OTHERS Notes Strobes are designed to flash at 1 flash per second mini from 20 31VDC Note that NFPA 72 1996 speci a flash rate of 1 to 2 flashes per second and ADA specify a flash rate of 1 to 3 flashes per sec All candela ratings represent minimum effective Strobe based on UL 1971 Sync Modules are rated for 3.0 amperes at 24 VDC Dual Sync Modules are rated for 3.0 amperes per cir The maximum number of interconnected DSM mod is twenty 20 Average current per actual Wheelock Production Testing at 20 24 31 VDC Diagrams for all models APPLIANCES SYNCHRONIZED WITH MULTIPLE DSM MODULES APPLIANCES SYNCHRONIZED WITH DSM MODULE SINGLE A NAC WITHOUT AUDIBLE SILENCE FEATURE APPLIANCE SYNCHRONIZED WITH SM MODULE SINGLE CLASS B NAC CIRCUIT AUDIBLE SILENCE FEATURE APPLIANCE NON SYNCHRONIZED AS and FACP must be set on continuous horn tone to achieve synchronized temporal code 3 tone and connected the SM or DSM Sync Module Wheelock products must be used within their published specifications and must be specified applied installed operated maintained and operationally tested in accordance with their installa instructions at the time of installation and at least twice a year or more often and in accordance with local state and codes regulations and laws Specification application installation operation maintenance and testing must be by qualified personnel for proper operation in accordance with all of the latest National Fire Protection Associa NFPA Underwriters Laboratories UL National Electrical Code NEC Occupational Safety and Health Adminis OSHA local state county province district federal and other applicable building and fire standards guidelines laws and codes including but not limited to all appendices and amendments and the requirements of the authority having jurisdiction AHJ CONTACT WHEELOCK FOR INSTALLATION INSTRUCTIONS P83509 Series AS AND GENERAL SHEET P82380 ON THESE PRODUCTS THESE DOCUMENTS DO UNDERGO PERIODIC IT IS IMPORTANT THAT YOU HAVE CURRENT INFORMATION ON THESE PRODUCTS THESE MATERI CONTAIN IMPORTANT INFORMATION THAT SHOULD BE READ PRIOR TO SPECIFYING OR INSTALLING PRODUCTS INCLUDING TOTAL CURRENT REQUIRED BY ALL DEVICES CONNECTED TO SYSTEM PRIMARY AND SECOND POWER SOURCES CIRCUITS FUSE RATINGS ON SIGNALING CIRCUITS TO HANDLE PEAK CURRENTS FROM ALL APPLIANCES ON COMPOSITE FLASH RATE FROM MULTIPLE STROBES WITHIN A PERSON FIELD OF VIEW THE VOLTAGE APPLIED TO THESE PRODUCTS MUST BE WITHIN THEIR RATED INPUT VOLTAGE OF 110 CANDELA STROBE PRODUCTS IN SLEEPING AREAS IN OFFICE AREAS AND OTHER SPECIFICATION AND INSTALLATION ISSUES USE SERIES AS ONLY ON CIRCUITS WITH CONTINUOUSLY APPLIED OPERATING VOLTAGE DO USE SERIES AS ON CODED OR INTERRUPTED CIRCUITS IN WHICH THE APPLIED VOLTAGE IS ON AND OFF AS THE STROBE MAY NOT FLASH FAILURE TO COMPLY WITH THE INSTALLATION INSTRUCTIONS OR GENERAL INFORMATION SHEETS RESULT IN IMPROPER INSTALLATION APPLICATION AND OR OPERATION OF THESE PROD IN AN EMERGENCY SITUATION WHICH COULD RESULT IN PROPERTY DAMAGE AND SERIOUS OR DEATH TO YOU AND OR OTHERS CONDUCTOR SIZE AWG LENGTH AND AMPACITY SHOULD BE TAKEN INTO CONSIDERATION TO DESIGN AND INSTALLATION OF THESE PRODUCTS PARTICULARLY IN RETROFIT IN Fike Corporation All rights reserved No previously 1163 are subject change without notice

Related Files