4XB SERIES SUPPLEMENT CONTAINS INFORMATION ABOUT THE SUPV2 JUMPER 50370 Rev A 50370 A ECN 95 404 Circuits Appliance Circuit Supervisory input is selected see section 3.7 both Notification Appliance Circuits will activate for supervisory To activate only one Notification Appliance Circuit Circuit 2 cut SUPV1 jumper To disable both Appliance Circuits cut SUPV2 jumper for supervisory conditions See figure below for jumper loca a 4XZM relay module is used relay 4 will activate for supervisory conditions a RZA 4X is used the red LED 4 will annunciate supervisory conditions Z Circuit 1 2 Watt part 71252 UL listed Bell Strobe Horn all 1 2 Watt part 71252 UL listed B B B OUT 1 OUT 2 12 04 95