4098 QuickConnect Smoke Sensors Instructions and Warnings NOT INSTALL ANY SIMPLEX PRODUCT THAT APPEARS DAMAGED Upon unpacking your Simplex product inspect the contents of carton for shipping damage If damage is apparent immediately file a claim with the carrier and notify Simplex HAZARD Disconnect electrical power when making any internal adjustments or repairs Servicing should be performed by qualified Representatives HAZARD Static electricity can damage components Therefore handle as follows Ground yourself before opening or installing components Keep uninstalled component wrapped in anti static material at all times TrueAlarm QuickConnect Smoke Sensors are connected to a 4010 4020 4100 or 4120 Fire Alarm Control Panel FACP by a single wire pair II or IDNet The 4098 9710 QuickConnect Smoke Sensor without Sounder is only compatible with the 4010 and obtains both power and data IDNet wiring The 4098 9713 QuickConnect Smoke Sensor with Sounder additionally requires 24VDC power for sounder operation and is not with the 2120 CDT document covers only the information necessary to mount and wire these sensor base configurations Before installing these devices make a survey of area to be covered in accordance with information provided in NFPA 72 Chapter 5 For specific applications refer to Simplex publication Common Requirements for Fire Alarm Systems Publication No FA2 91 010 For additional information refer to NFPA 72 and the NEMA Guide for Proper of System Smoke Detectors Refer to the 4098 Detectors Sensors and Bases Application Manual 574 709 that was shipped with the fire alarm system for compatibility and data address settings maintenance and correct application of these QuickConnect Smoke Sensors the sensors described in this instruction in accordance with applicable NFPA standards local codes and the having jurisdiction Failure to follow these instructions may result in failure of the sensor to initiate an alarm Simplex is not responsible for sensors that have been improperly installed tested or maintained smoke sensors come with dust covers to protect them from contamination during completion of building construction will not operate with dust covers in place Do not over tighten mounting screws when mounting either the 4098 9832 Adapter Plate or the QuickConnect Sensor Mounting Plate Tighten the screws without warping the adapter or mounting plate s 4098 QuickConnect Smoke Sensors mount to a 4 inch square single gang or 4 inch octagonal electrical box Install the QuickConnect Smoke Sensor Figure 1and the notes as a reference the 4098 9822 Relay Module requires an 1 extension ring not supplied mounted to the 4 inch square or octagonal electrical relay module s cannot be used in single gang electrical box installations to meet the space requirement of the relay module and its The 4098 9822 relay module MUST BE installed in the electrical box directly behind the 4098 9713 QuickConnect Smoke Sensor Sounder MOUNTED TO BE FLUSH OR RECESSED 1 4 MAX GANG 2 1 8 DEEP BOX SUPPLIED 10.16cm x 1 1 2 DEEP BOX NOT SUPPLIED 10.16cm x 1 1 2 DEEP BOX SUPPLIED PLATE KIT FOR 4 SQUARE MOUNTED BOX CONNECT SENSOR PLATE SCREW WASHER UNTIL SNUG LBS 8 32 x 1 1 4 MACHINE UNTIL SNUG IN LBS STRIP STRIP CONNECT SENSOR ATTACHMENT 8 32 x 1 1 2 MACHINE UNTIL SNUG IN LBS 8 x 1 THREAD FORMING SCREW UNTIL SNUG IN LBS 2 the wires through the hole of the mounting plate the mounting plate to the electrical box or adapter plate as with tabs facing towards devices DO NOT OVERTIGHTEN Connect the wires to the terminal strip provided loose according to Connect terminal strip to the PCA Header pin strip located on the Smoke Sensor terminal strip must be positioned to the PCA header pin strip and not at an angle Push at each end of the terminal strip with an even load until it is fully onto the header the QuickConnect Smoke Sensor to the adapter plate pushing the back into the electrical box and give a clockwise turn to attach Using the 4098 9822 relay module requires an 1 extension ring supplied mounted to the 4 inch square or octagonal electrical box meet the space requirement of the relay module and its wire The module cannot be used in single gang electrical box installations relay module 4098 9822 MUST BE installed in the electrical box behind the QuickConnect Smoke Sensor 4098 9713 can be mounted to a single gang 3 deep electrical ONLY when 16 AWG or smaller wire is used 1 QuickConnect Smoke Sensor Mounting 2000 Simplex Time Recorder Co Westminster MA 01441 0001 USA 2000 Simplex International Time Equipment Co Ltd Mississauga Ontario L4V 1H3 Canada specifications and other information shown were current as of publication and are subject to change without notice E 2 illustrates the wiring connections for the different QuickConnect Smoke Sensor configurations All screw terminals accept 14 to 18 gauge AWG solid or wire Recommended strip length is 3 8 inch Maximum torque should not exceed 3.5 inch pounds Connect wiring to terminals as illustrated in Figure 2 wire runs to provide supervision USED NOTE 7 NOTE 7 OTHER DEVICES REMOTE LED 4098 9822 RELAY NOTE 1 OTHER IDNet NOTE 2 OTHER DEVICES NOTE 5 NOTE 6 C NC NO C NC NO A NOTE 4 B NOTE 4 IS OPTIONAL SEE NOTE 3 USED OTHER DEVICES USED LED NOTE 1 II IDNet II IDNet OTHER NOTE 2 II IDNet II IDNet II IDNet NOTE 6 II IDNet OTHER NOTE 2 IS OPTIONAL SEE NOTE 3 TERMINAL STRIP TERMINAL STRIP Remote LED and relay wires are not supervised Maximum quantity of devices per circuit is 127 for 4020 4100 or 4120 FACP and 250 for the 4010 FACP Maximum quantity of 4098 9713 sensors when is coded Temporal Code is 43 shield is used twist shield wires together and cap with wire nut Shield should be insulated from electrical box to 32VDC 008 amperes typical 013 amperes max Contact A or B Dry Form C each rated 2 amperes at 24VDC 0.5 amperes at 110VAC resistive Do not use remote LED if the 4098 9822 relay module is used is ONLY compatible with 4010 FACP 2 4098 QuickConnect Smoke Sensors Connections or following an 8 Digit Product ID number denotes ULC listed product following an eight digit Product ID number denotes Global product The 2nd identifies market country models with this suffix are not UL Listed II Communication Net is protected by U S Patent No 4,796 025 is a trademark of Simplex Time Recorder Company E